Deep Sea Controller – How To Test A Generator WITH Load – DSE 7310

Using the Generator Control Panel In the Plant Room

Generator – at all times the generator is in Auto

Generator control panel Auto button

This button red light must always lit

to ensure the generator remains in automatic mode ready to take load during any power outage.

Monthly ON Load Test will place all the building load on the generator.

This test is using the control panel – main distribution board in plant room.

To begin monthly ON load test Press manual button ONCE

Red light will be litYou are now in manual mode.

Press the Green MODE button repeatedly until Test on Load is shown on the display.

Press the tick button ONCE to confirm the change.

A LED indicator beside the button confirms this action.

The Generator Will Now Start – Leave generator to run for 15 minutes

To STOP ON Load test press the Red Stop button

Press the Auto button        

to bring the generator back into automatic mode.

Generator – at all times the generator is in Auto

Generator control panel Auto button

This button red light must always lit to ensure the generator is in automatic mode ready to take load during any power outage.

 

Download our PDF guide:

How to test a generator with load-DSE 7310

Search – Knowledge Base

Talk to Us: