Diesel Generator Fuel Consumption Chart.

The page provides approximate fuel consumption figures for diesel generators ranging from 50kVA to 3000kVA at 50% and 100% load, noting that these figures can vary based on generator efficiency and fuel condition. For inquiries about diesel generators, there's a contact number provided.

Approximate Fuel Consumption for Diesel Generator sized from 50kVA to 3000kVA.

We have approximately calculated the Diesel consumption for 50% load (litres/hr) and 100% load (litres/hr).

All fuel consumption figures are approximate and subject to change by various factors, including the efficiency of the generator and condition of the fuel.

Generator Size (kVA) Generator Size (kW) Fuel Consumption at 50% Load (L/hr) Fuel Consumption at 100% Load (L/hr)
50 kVA 40 kW 6 12
75 kVA 60 kW 9 18
100 kVA 80 kW 12 23
150 kVA 120 kW 17 34
200 kVA 160 kW 23 46
250 kVA 200 kW 28 56
350 kVA 280 kW 40 80
500 kVA 400 kW 57 114
800 kVA 640 kW 90 179
1000 kVA 800 kW 112 224
1250 kVA 1000 kW 137 275
1500 kVA 1200 kW 165 330
1750 kVA 1400 kW 192 385
2000 kVA 1600 kW 220 440
2250 kVA 1800 kW 248 495
2500 kVA 2000 kW 275 550
3000 kVA 2400 kW 330 660

* All fuel consumption figures are approximate and subject to change by various factors, including the efficiency of the generator and condition of the fuel.