Deep Sea Controller – How To Test A Generator OFF Load – Weekly – DSE 6110
HOW TO PERFORM A MANUAL OFF LOAD TEST
1. Turn Breaker on the Generator to OFF position
2. Press Manual Mode button on display ONCE only
3. Check Manual Mode LED is lit
4. Check Display Reads Manual Mode.
5. PRESS GREEN Start Button for Approx 2 seconds Engine will start up and begin the OFF load test
Close generator door until the test is over
5.b If Engine fails to start, check screen for any faults, check fuel level clear faults using reference manual if possible.
5.c Repeat steps 4 – 5
5.d If engine still fails to start contact Power continuity Systems 0845 055 8455, Mobile Numbers 07770 236866 / 07903227774
6. Run Engine for approximately 5 Minutes
Press RED OFF Button ONCE to STOP engine
Press Auto Button ONCE and check Auto LED is illuminated
Check Display Reads Auto Mode
When the OFF Load test in Complete Turn the Breaker on the Generator back to ON position